Up

Rockleigh Volunteer Fire Department

ROCKLEIGH FIRE DEPARTMENT

 

Borough Of Rockleigh

26 Rockleigh Road

Rockleigh, New Jersey 07647

 

Protecting Rockleigh Borough since 1932"

 

 

SOP 14: PUMP OPERATIONS

 

 

A. MINIPUMPER OPERATION

1. Arrival on scene:

a. Lay a 3-inch supply line to the fire scene from a hydrant or from a convenient location for relay hook-up from a Maxipumper, such as the beginning of a driveway.

b. Stop pumper in a safe position that gives adequate access, but does not block access for subsequent apparatus.

c. Place transmission in neutral, engage parking brake.

d. Engage Power Take-Off (PTO) by depressing clutch and pulling Pump-Shift Knob over transmission up fully. Release the clutch, a noticeable change in sound will be heard.

e. Set wheel chocks.

2. Water-tank operation:

a. Open "tank-to-pump" gate.

b. Advance throttle until compound-gage pressure reaches 75 - 100 psi. (If necessary, prime pump until pressure registers on compound gage.)

c. Open appropriate discharge gates [Ensure that hose is fully out of bed.]

d. Advance throttle until compound-gage pressure reaches 125 psi.

e. Monitor water supply. Keep officer informed of water supply. Watch and listen for signs of running out of water, such as sudden drop in compound-gage pressure. Upon loss of water, immediately shut down pump until a supply line is hooked up and a water supply re-established.

3. Supply-line operation:

a. Connect 3-inch supply line to suction inlet.

b. Open "suction inlet" gate, slowly.

c. Open appropriate discharge gates. [Ensure that hose is fully out of bed.]

d. Advance throttle until compound-gage pressure reaches 125 psi.

4. Combined Water-Tank and Supply-Line Operation:

a. Proceed through Water-tank operation (Section 2 above).

b. Connect the 3-inch supply line to suction inlet.

c. Open "suction inlet" gate, slowly, watching compound gage pressure.

d. Retard throttle to maintain 125 psi as the water supply reaches the pump. [If pumping from tank and the suction intake is opened, the 100 psi pressure in the Hackensack water system will add to the at 125 psi pump pressure to give 225 psi - dangeriously too much to control at the nozzle.]

e. Close the tank-to-pump gate immediately. [Back flow of municipal water through the pump into the tank may (and has) burst the tank on R-1.]

5. Attack lines:

a. Booster lines: Open Left and/or Right Booster Gate(s). Pull sufficient hose from reels. [125 psi provides a 20 GPM flow through 100-feet of 1-inch hose.] Booster lines should be used only for brush fire or wash-down purposes. There is insufficient flow for knockdown of any other type of fire and, as such, can be a danger to firefighters.

b. 1-1/2 attack lines: Remove line(s) completely from hose beds. Open left and/or right Preconnect Gate(s) when requested.

c. Adjust pressure to 125 psi at discharge gate pressure gage(s). [125 psi provides a 60 GPM flow through 200-feet of 1/2-inch hose.; 165 psi produces 100 GPM which is the limit of the nozzle]

d. Foam:

(1) Use LEFT 1-1/2-inch PRE-CONNECT only.

(2) Rotate valve over the pump panel to educt foam from the 12-gallon foam tank into the left pre-connect discharge.

(3) Increase discharge pressure to 175 psi to educt foam. [Foam will not aspirate through the eductor without sufficient pressure.]

 

B. MAXIPUMPER OPERATION

1. Arrival on scene:

a. Lay a 5-inch supply line to the fire scene from a hydrant .

b. Stop pumper in a safe position which gives adequate access, but does not block access for subsequent apparatus.

c. Place transmission in neutral, engage parking brake.

d. Engage Power Take-Off

(1) Pull Pump-Shift Knob out fully (located on left side of dash panel). [If knob does not move, it may be in locked position. Rotate knob, then pull out]. Adjacent amber "pump-indicator" lights up when PTO engages.

(2) Place transmission in drive. Engage safety latch on gear shift.

e. Set wheel chocks.

2. Water-tank operation:

a. "Pump-Indicator" light must be green on pump panel. [If not on, repeat above steps for engaging PTO.]

b. Pressure-Volume valve must be at VOLUME setting.

c. Open "tank-to-pump" gate.

d. Advance throttle until compound-gage pressure reaches 75 - 100 psi. [If necessary, prime pump until pressure registers on compound gage.]

e. Determine which hose and discharge port is to be used. [Ensure that hoses are fully out of beds before charging.]

f. Open appropriate discharge gates when water is called-for.

g. Adjust throttle until compound-gage pressure reaches 125 psi.

h. Monitor water supply. Keep officer informed of water supply. Watch and listen for signs of running out of water, such as sudden drop in compound-gage pressure. Upon loss of water, immediately shut down pump until supply line is hooked up and water supply re-established.

3. Supply-line operation:

a. Connect 5-inch supply line to suction inlet. Signal the hydrant man to open the hydrant.

b. Bleed line of air, using the intake manifold bleed cocks.

c. Open "suction inlet" gate, slowly. Note increase in pressure on the compound gage.

d. Determine which hose and discharge port is to be used. [Ensure that hoses are fully out of beds before charging.]

e. Open appropriate discharge gates.

f. Advance throttle until compound-gage pressure reaches 125 psi

g. Monitor water supply. Keep officer informed of water supply and Incident Command Officer informed of any drop in supply pressure. Watch and listen for signs of running out of water, such as sudden drop in compound-gage pressure or softening of supply line. Upon loss of water, immediately shut down pump until supply is restored. [Try to anticipate interruption of water supply so that hose teams can be backed out before total loss occurs.]

4. Combined operation:

a. Proceed through Water-tank operation (Section 2 above).

b. Connect the 5-inch supply line to "suction inlet".

c. Bleed line of air, using bleed cocks on intake manifold.

d. Open "suction inlet" gate slowly, watching compound gage pressure.

e. Retard throttle to maintain 125 psi as the water supply reaches the pump. [When pumping from tank and the suction intake is opened, the 100 psi pressure in the Hackensack water system will add to the at 125 psi pump pressure to give 225 psi - far too much to control at the nozzle.]

f. Close the tank-to-pump gate immediately. [Back flow of municipal water through the pump into the tank may (and has) burst tanks.].

g. Re-fill tank when time permits, using "Tank-Fill" gate.

5. 2-inch Attack Lines:

a. 2-inch PRE-CONNECTS: Remove line(s) completely from hose beds. Open Preconnect Gate(s) when requested. If a gated wye-reducer is attached to a discharge port, ensure that the appropriate gated wye is open.

b. Adjust pressure to 125 psi at opened discharge gate pressure gage(s). 125 psi provides a 125 GPM flow through 200-feet of 2-inch hose; 150 psi provides 200 GPM which is the limit of the automatic nozzles.

c. Foam:

(1) Insert foam eductor into line using 10-foot section of 2-inch hose.

(2) Increase discharge pressure to 175 psi to educt foam. [Foam will not aspirate through the eductor without sufficient pressure.]

(3) Use portable aspirator to suck up foam from 5-gallon foam buckets.

6. Master streams:

a. Sprinkler lines:

(1) Run a 3-inch line from a 2½-inch discharge to the sprinkler connection.

(2) Charge line at no more than municipal pressure (125 psi or less) .

(3) Run a second 3-inch line from another 2½-inch discharge port to the sprinkler connection.

b. 3-inch and 5-inch supply lines:

(1) Run one 3-inch line from a 2½-inch discharge port or a 5-inch line from the married 5-inch discharge port to the appropriate suction intake.

(2) Charge and maintain supply line at municipal pressure (125 psi or less).

c. 3-inch manifold lines:

(1) Run a 3-inch line from a 2½-inch discharge port to a 2-1/2-inch gated wye reducer. Two 2-inch attack lines run from the gated wye.

(2) Maintain a pressure of 150 psi. [Longer hose lays require only slightly higher pressure. ]

d. 5-inch manifold lines:

(1) Run a 5-inch line from the 5-inch discharge port to a 5-inch manifold.

(2) Maintain a pressure of 125 - 150 psi. Four 2-inch or 2-1/2-inch attack lines can run from a manifold supplied by a 5-inch line.

e. 2-1/2-inch Hand lines:

(1) 2-1/2-inch master streams may be connected to discharge ports, gated wye reducers, or 5-inch manifolds.

(2) 2-1/2-inch hand lines are charged at 125 psi, which provides a 250 GPM flow through 200-feet of 2-1/2-inch hose. It will take two or three firemen at the nozzle to control this line.

f. Deluge gun:

(1) Use open-bore tips of the largest possible size for maximum penetration into a large body of fire.

(2) Use the adjustable nozzle 500 GPM nozzle for smaller fire and exposure protection.

(3) Use the 250 GPM aspirating nozzle for foam.

History: Prepared by: EW April

 

 

Home Up 1. Response 2. Mutual Aid 3. Medical Aid 4. Residence Fires 5. Non-Sprinklered 6. Sprinklered Fires 7. Vehicular Fires 8. Brush Fires 9. Dumpster Fires 10. Haz-Mat 11. Disasters 12. SCBA 13. Company Ops. 13A. Evacuation 13B. Engine Co. Ops. 13C. Ladder Co. Ops. 14. Pump Ops. 15. I.C.S. 16. Communications 17. F.A.S.T. Teams